Quick answer
On a conventional portable generator, the engine speed sets the frequency of the electricity. In North America, household power is 60 Hz, and a typical two-pole portable generator makes that by running at about 3,600 RPM. In areas with 50 Hz power, the same design runs at about 3,000 RPM. If the speed drifts, the frequency and the voltage drift with it.
The relationship
For an alternator, frequency in hertz equals the number of poles multiplied by the RPM, divided by 120.
- 2 poles at 3,600 RPM: 2 × 3,600 ÷ 120 = 60 Hz
- 4 poles at 1,800 RPM: 4 × 1,800 ÷ 120 = 60 Hz
- 2 poles at 3,000 RPM: 2 × 3,000 ÷ 120 = 50 Hz
Most portable generators use the two-pole design because it works well with small, fast engines. Some larger or quieter units use four poles at about 1,800 RPM, which tends to mean a larger, heavier machine, but does not suit every size of generator.
Why a governor holds a steady speed
An engine’s speed would naturally change with the load. The governor, either mechanical or electronic, adjusts the throttle to keep the speed near the target as the load changes. That keeps frequency, and therefore voltage, within a usable range. If you want to learn how a small engine governor is set, see how to adjust the governor on a small engine.
Many generators run a little faster, and give a little higher voltage and frequency, with no load, then settle toward the rated values when loaded. The manual will list the normal range. A small difference is typically normal, while a large one is not.
Voltage and speed
Voltage in a conventional generator is also tied to engine speed. If speed falls by a noticeable amount, voltage falls too. This is why a laboring engine under overload gives low voltage and why a generator with a dirty carburetor can give weak output. See generator low voltage output and generator overload symptoms. A lot of speed variation can also show up as generator surging.
Running too fast is a problem as well. Excess speed produces excess voltage and frequency that can damage motors and electronics, and puts extra stress on the engine. Do not turn up the speed to compensate for low voltage.
Inverter generators
Inverter generators produce AC, turn it into DC, then create clean 60 Hz AC electronically. Because of that, the engine speed does not need to match the frequency, and many models change engine speed to suit the load. The engine speeding up and down is normal on these units, and the manual rarely gives a specific RPM target for adjustment.
Checking speed
If you suspect the speed is off:
- Use a tachometer made for small engines or a frequency meter, if you have one. Many digital multimeters can read frequency (Hz), though read the meter’s instructions first.
- Check at no load and at a moderate load.
- Check the manufacturer’s specification before adjusting anything.
Adjustment is usually a small screw or spring tension on the governor linkage. Make only small changes, check against a meter, and do not exceed the specification. If you cannot get stable output, there may be a fuel or electrical issue; see generator running but no power.
What goes wrong
- A worn or misrouted governor spring
- Binding linkage
- Fuel problems that stop the engine from holding speed (see how to clean a generator carburetor)
- Altitude or temperature changes that affect engine power
- Overloading that pulls the speed down